XWEB5000: MONITORING, CONTROLLING and SUPERVISING
Power supply 110÷230Vac
LAN output pres
USB output 2
RS485 output pres
Relay output 3
Digital input pres
Print output 25 pin
Keyboard/mouse output pres
Video output pres
Sampling time from 1 to 255 minutes
External modem analogue
Internal modem analogue optIt is provided with a powerful supervision engine suited for larger installations (with up to 247 devices) in the refrigeration,
conditioning and building automation field, where it is necessary to program several different interactive actions that the
controller has to perform. It is extremely well suited to hypermarkets, large storage and distribution centres, as well as production
and storage goods processing and is ideal for the large service center (modem, ethernet and internet connection). The system
manages the alarm transmission to the “in charge” service (via FAX, e-mail, SMS and also through relay outputs) and it can also
work without a PC using direct connection of a monitor, keyboard and mouse. Local or remote connection PC is made using
Microsoft Internet Explorer® and Firefox® browser.
• Monitoring, controlling and supervising web server connection to Dixell’s controllers with serial output and to other
ModBUS-RTU compatible devices
• 19” RACK or desk mounting
• Built-in editor with local and field simulator
• Quick and easy connection to Web pages with dedicated interface for PDA/Smartphone
• All controller values can be displayed using a special “Single View” window or a “Run Time” window with many controllers
viewed at the same time. The ability to use a “Layout” view of the plant with pictures and schematic drawings is also an
option
• Complete and simplified analysis of the unit functioning thanks to a powerful tool that allows to view data in graphical
format (Excel®)
• One year of stored data inside the XWEB memory (one year of stored data with 15min sampling time)
• Easy plant management by means of the “Scheduler” to send commands according to a custom calendar
• Calendar function and internal RTC both for alarm transmission to the “in charge” service and command sending to the
controllers
• Possibility to divide the controllers set in different categories of products with their own sampling time
• Ability to select particular data on which to perform the monitoring with reduced sampling time
• Alarm sending via FAX, SMS or e-mail
• Commands sending activation through digital input
• Standard communication protocol ModBUS-RTU
• 50VA max power absorption
• DPC (Dew Point Control) for anti-sweat heater management - Lisätiedot
-