- Kuvaus
-
Kuvaus
ADVANCED MULTIFUNCTION CONTROLLER FOR CHILLER/HEAT PUMP WITH 1 CIRCUIT AND 1 COMPRESSOR
CX: 32x74mm
Generals
N° digits display: first: ± 4 d.p. second: ± 4 d.p.
Power supply: 12Vac/dc, 24Vac/dc optional
Probe inputs
Pb1: NTC configurable
Pb2: NTC configurable
Pb3: NTC / 4-20mA / 0,5V configurable
Pb4: NTC / digital input configurable
Digital inputs
High pressure: present
Low pressure: present
N° 4: configurable
Relay outputs
RL1 Compressor 1: * 8A
RL2: * 8A configurable
RL3: 8A configurable
RL4: * 8A configurable
RL5: * 8A configurable, optional
Other outputs
Analog output for fan speed module: 4-20mA optional or 0-10mA optional
Signal output for triac or ON/OFF fan module: ° PWM
Open collector output: 12Vdc-40mA max
Remote keyboards: VICX610
Serial output: TTL
Hot Key / Prog Tool Kit output: present
Other
Triac module inside: 2A optional
RTC: optional
Buzzer: optional
* With triac module: RL1 = 5A - RL2 = 5A - RL4 = 5A config - RL5 = not present
° PWM output becames output configured for aux relay control, when the triac is incorporatedIC100 SERIES: 1 CIRCUIT up to 2 COMPRESSOR UNIT CONTROLLERS
IC100CX is Dixell’s answer to real management and control requirements of chiller units and heat pumps single circuit
(gas and water reversibility) with up to two compressors or a single compressor with capacity stages, by means of a compact
instrument with the possibility of controlling units like: air/air, air/water, water/water, motor-condensing.TECHNICAL DATA
Housing self extinguishing ABS
Format frontal 32x74mm; depth 59,5mm
Display 4 digits red LED + 4 digits yellow LED + icons
Mounting panel mounting in a 29x71mm cut-out
Front protection IP65
Connections disconnectable connectors 12-14 or 14-6 pins
Power supply 12Vac/dc -10% ÷ +15%, 24Vac/dc ±10% 50/60Hz
Power absorption 5VA max
Relay outputs SPDT 8(3)A, 250Vac (SPDT 8(3)A + 3 SPST 5(2)A; 250Vac for model with triac)
External relay output 12Vdc - 40mA maxAnalog outputs
PWM signal (single-fan module)
4-20mA (fan module)
0-10V (fan module)Data storing non-volatile memory (EEPROM)
Operating temperature -10-60°C (14-140°F)
Storage temperature -30-85°C (-22-185°F)
Relative humidity 20-85% (non condensing)Measuring and regulation range
pressure probe: 0-50bar
NTC probe: -40-110°C (-40-230°F)Resolution 0,1°C or 1°F or 0,1bar or 1PSI
Accuracy (at ambient temperature) ± 0.7°C ± 1 digit
• Twin compressor functioning
• Function of compressor capacity stages for high and low condensing pressure
• ON/OFF or variable speed condensing fan control without the need to use external devices
• Forced and combined defrost
• Energy saving for time band or digital contact
• Internal data logger with up to 50 alarms
• Real time clock
• Voltage output for additional external relay management
• 4÷20mA/0÷10V output for condensing fan management
• Analog input configurable as NTC, 4÷20mA and 0÷5V ratiometric
• Configurable relays, probes and digital inputs
• Easy programming through HOT KEY or PC (WIZMATE PROG TOOL KIT)
• TTL (convertible in RS485) serial output with ModBUS protocol
• Quick tab connectors on all models - Lisätiedot
-
Lisätiedot